ORDINANCE NO. _______
AN ORDINANCE OF THE CITY OF LAWRENCE, KANSAS REPEALING ARTICLE 5 OF CHAPTER V OF THE CODE OF THE CITY OF LAWRENCE, KANSAS, 2009 EDITION, AND AMENDMENTS THERETO; AND ADOPTING THE INTERNATIONAL PLUMBING CODE, 2009 EDITION, AND EXCEPTING, AMENDING AND MODIFYING CERTAIN OF ITS PROVISIONS.
BE IT ORDAINED BY THE GOVERNING BODY OF THE CITY OF LAWRENCE, KANSAS:
Section 1. Article 5 of Chapter V of the Code of the City of Lawrence, Kansas, 2009 Edition and amendments thereto, is hereby repealed.
Section 2. Article 5 of Chapter V of the Code of the City of Lawrence, Kansas, 2009 Edition and amendments thereto, is enacted to read as follows, the intent being to replace the current provisions:
ARTICLE 5. PLUMBING
5-501 PLUMBING CODE INCORPORATED.
The International Plumbing Code, 2009 Edition, published by the International Code Council, is hereby adopted by reference as if it were fully set out in this article, except for those portions that are hereinafter deleted, modified or amended.
5-502 SAME.
Not less than one (1) copy of the International Plumbing Code, 2009 Edition, marked or stamped in the manner provided by K.S.A. 12-3010, with all sections or portions thereof intended to be omitted clearly marked and showing portions that are amended and to which shall be attached a copy of amendments, shall be filed with the City Clerk and shall be open to inspection and available to the public at reasonable business hours. Official copies of such Code shall be supplied at the cost of the City to the officials and agencies in the manner listed and set forth in K.S.A.12-3010. Subsequent references to the "International Plumbing Code" or "Standard Code" shall mean the "International Plumbing Code, 2009 Edition”, as adopted herein.
5-503 SEVERABILITY.
If any section, clause, sentence, or phrase of this Article is found to be unconstitutional or is otherwise held invalid by any court of competent jurisdiction, it shall not affect the validity of any remaining parts of this Article.
5-504 AMENDMENTS MADE TO THE INTERNATIONAL PLUMBING CODE, 2009 EDITION.
The International Plumbing Code is amended or changed as follows. The amendment of any section shall not serve to amend or repeal any other discretely numbered provision of the code, whether or not such provision is considered a section or subsection, unless that section or subsection is specifically referenced in the ordinance.
5-505 Chapter 1 of the International Plumbing Code is hereby deleted.
5-506 Section 407 of the International Plumbing Code and the indicated subsections are hereby amended to read as follows:
407.1 Approval. Bathtubs shall conform to ANSI Z124.1, ASME A112.19.1M, ASME A112.19.4M, ASME A112.19.9M, CSA B45.2, CSA B45.3 or CSA B45.5.
407.2 Bathtub waste outlets. Bathtubs shall have waste outlets a minimum of 1.5 inches (38 mm) in diameter. The waste outlet shall be equipped with an approved stopper.
407.3 Glazing. Windows and doors within a bathtub enclosure shall conform to the safety glazing requirements of the International Building Code.
407.4 Bathtub enclosure. Doors within a bathtub enclosure shall conform to ASME A112.19.15.
407.5 Prohibited location. In no case shall tubs be installed head to head.
5-507 Table 605.3 of the International Plumbing Code is hereby amended to read as follows:
TABLE 605.3
WATER SERVICE PIPE
MATERIAL |
STANDARD |
|
|
Asbestos-cement pipe |
ASTM C 296 |
Brass pipe |
ASTM B 43 |
Chlorinated polyvinyl chloride (CPVC) plastic pipe |
ASTM D 2846; ASTM F 441; ASTM F 442; CSA B137.6 |
Copper or copper-alloy pipe |
ASTM B 42; ASTM B 302 |
Copper of copper-alloy tubing (Type K, WK, L, WL, M or WM) |
ASTM B 75; ASTM B 88; ASTM B 251; ASTM B 447 |
Cross-linked polyethylene (PEX) plastic tubing |
ASTM F 876; ASTM F 877; CSA B137.5 |
Cross-linked polyethylene/aluminum/cross-linked polyethylene (PEX-AL-PEX) pipe |
ASTM F 1281; ASTM F 2262; CAN/CSA B187.10M |
Cross-linked polyethylene/aluminum/high-density polyethylene (PEX-AL-HDPE) |
ASTM F 1986 |
Ductile iron water pipe |
AWWA C151; AWWA C115 |
Galvanized steel pipe |
ASTM A 53 |
Polyethylene (PE) plastic pipea |
ASTM D 2239; ASTM D 3035; CSA B137.1 |
Polyethylene (PE) plastic tubinga |
ASTM D 2737; CSA B137.1 |
Polyethylene/aluminum/polyethylene (PE-AL-PE) pipea |
ASTM F 1281; CAN/CSA B137.9 |
|
|
Polyvinyl chloride (PVC) plastic pipea |
ASTM D 1785; ASTM D 2241; ASTM D 2672; CSA B137.2 |
Stainless steel pipe (Type 304/304L) |
ASTM A 312; ASTM A 778 |
Stainless steel pipe (Type 316/316L) |
ASTM A 312; ASTM A 778 |
a Limited to the retrofitting of an existing lawn irrigation system, which was installed prior to August 1, 1992.
5-508 Table 605.4 of the International Plumbing Code is hereby amended to read as follows:
TABLE 605.4
WATER DISTRIBUTION PIPE
MATERIAL |
STANDARD |
Brass pipe |
ASTM B 43 |
Chlorinated polyvinyl chloride (CPVC) plastic pipe or tubing |
ASTM D 2846; ASTM F 441; ASTM F 442; CSA B137.6 |
Copper or copper-alloy pipe |
ASTM B 42; ASTM B 302 |
Copper or copper-alloy tubing (Type K, WK, L, WL, M or WM) |
ASTM B 75; ASTM B 88; ASTM B 251; ASTM B 447 |
Cross-linked polyethylene (PEX) plastic tubing |
ASTM F 876; ASTM F 877; CSA B137.5 |
Cross-linked polyethylene/aluminum/cross-linked polyethylene (PEX-AL-PEX) pipe |
ASTM F 1281, ASTM F 2262; CAN/CSA B137.10M |
Cross-linked polyethylene/aluminum/high-density polyethylene (PEX-AL-HDPE) |
ASTM F 1986 |
Ductile iron pipe |
AWWA C151/A21.51; AWWA C115/A21.15 |
Galvanized steel pipe |
ASTM A 53 |
|
|
|
|
Stainless steel pipe (Type 304/304L) |
ASTM A 312; ASTM A 312; ASTM A 778 |
Stainless stell pipe (Type 316/316L) |
ASTM A 312; ASTM A 778 |
5-509 Section 708.3 of the International Plumbing Code and the indicated subsections are hereby amended to read as follows:
708.3 Where required. Cleanouts shall be located in accordance with Sections 708.3.1 through 708.3.6.
708.3.1 Horizontal drains within buildings. All horizontal drains shall be provided with cleanouts located not more than 100 feet (30 480 mm) apart.
708.3.2 Building sewers. Building sewers shall be provided with cleanouts located not more than 100 feet (30 480 mm) apart measured from the upstream entrance of the cleanout. For building sewers 8 inches (203 mm) and larger, manholes shall be provided and located not more than 200 feet (60 960 mm) from the junction of the building drain and building sewer, at each change in direction and at intervals of not more than 400 feet (122 m) apart. Manholes and manhole covers shall be of an approved type.
708.3.3 Changes of direction. Cleanouts shall be installed at each change of direction greater than 45 degrees (0.79 rad) in the building sewer, building drain and horizontal waste or soil lines. Where more than one change of direction occurs in a run of piping, only one cleanout shall be required for each 40 feet (12 192 mm) of developed length of the drainage piping.
708.3.4 Base of stack. A cleanout shall be provided at the base of each waste or soil stack.
708.3.5 Building
drain and building sewer junction. There shall be a cleanout near the junction
of the building drain and the building sewer. The cleanout shall be either
inside or outside the building wall and shall be brought up to the finished
ground level or to the basement floor level. An approved two-way
cleanout is allowed to be used at this location to serve as a required cleanout
for both the building drain and building sewer. The cleanout at the
junction of the building drain and building sewer shall not be required if the
cleanout on a 3-inch (76 mm) or larger diameter soil stack is located within a
developed length of 10 feet (3048 mm) of the building drain and building sewer
connection. The minimum size of the cleanout at the junction of the
building drain and building sewer shall comply with Section 708.7.
708.3.6 Manholes. Manholes serving a building drain shall have secured gas-tight covers and shall be located in accordance with Section 708.3.2.
5-510 Section 710.1 of the International Plumbing Code and the indicated subsections are hereby amended to read as follows:
710.1 Maximum fixture unit load. The maximum number of drainage fixture units connected to a given size of building sewer, building drain or horizontal branch of the building drain shall be determined using Table 710.1(1); however no building sewer shall be less than four (4) inches in diameter. The maximum number of drainage fixture units connected to a given size of horizontal branch or vertical soil or waste stack shall be determined using Table 710.1(2).
710.1.1 Horizontal stack offsets. Horizontal stack offsets shall be sized as required for building drains in accordance with Table 710.1(1), except as required by Section 711.4.
710.1.2 Vertical stack offsets. Vertical stack offsets shall be sized as required for straight stacks in accordance with Table 710.1(2), except where required to be sized as a building drain in accordance with Section 711.1.1.
5-511 Section 916 of the International Plumbing Code and the indicated subsections are hereby amended to read as follows:
916 Vent Pipe Sizing
916.1 Size of stack vents and vent stacks. The minimum required diameter of stack vents and vent stacks shall be determined from the developed length and the total of drainage fixture units connected thereto in accordance with Table 916.1, but in no case shall the diameter be less than one-half the diameter of the drain served or less than 1¼ inches (32 mm).
916.2 Vents other than stack vents or vent stacks. The diameter of individual vents, branch vents, circuit vents and relief vents shall be at least one-half the required diameter of the drain served. The required size of the drain shall be determined in accordance with Table 710.1(2). Vent pipes shall not be less than 1¼ inches (32 mm) in diameter. Vents exceeding 40 feet (12 192 mm) in developed length shall be increased by one nominal pipe size for the entire developed length of the vent pipe. Relief vents for soil and waste stacks in buildings having more than 10 branch intervals shall be sized in accordance with Section 914.2.
916.3 Developed length. The developed length of individual, branch, circuit and relief vents shall be measured from the farthest point of vent connection to the drainage system to the point of connection to the vent stack, stack vent or termination outside of the building.
916.4 Multiple branch vents. Where multiple branch vents are connected to a common branch vent, the common branch vent shall be sized in accordance with this section based on the size of the common horizontal drainage branch that is or would be required to serve the total drainage fixture unit (dfu) load being vented.
916.4.1 Branch vents exceeding 40 feet in developed length. Branch vents exceeding 40 feet (12 192 mm) in developed length shall be increased by one nominal size for the entire developed length of the vent pipe.
916.5 Sump vents. Sump vent sizes shall be determined in accordance with Sections 916.5.1 and 916.5.2.
916.5.1 Sewage pumps and sewage ejectors other than pneumatic. Drainage piping below sewer level shall be vented in a similar manner to that of a gravity system. Building sump vent sizes for sumps with sewage pumps or sewage ejectors, other than pneumatic, shall be determined in accordance with Table 916.5.1.
916.5.2 Pneumatic sewage ejectors. The air pressure relief pipe from a pneumatic sewage ejector shall be connected to an independent vent stack terminating as required for vent extensions through the roof. The relief pipe shall be sized to relieve air pressure inside the ejector to atmospheric pressure, but shall not be less than 1¼ inches (32 mm) in size.
916.6 Total Size of Vents. The drainage piping of each building and each connection to a public sewer or a private sewage disposal system shall be vented by means of one or more vent pipes, the aggregate cross-sectional area of which shall not be less than that of the largest required building sewer, as determined from Table 710.1(1). Vent pipes from fixtures located upstream from pumps, ejectors, backwater valves, or other devices that in any way obstruct the free flow of air and other gases between the building sewer and the outside atmosphere shall not be used for meeting the cross-sectional area venting requirements of this section.
Exception: When connected to a common building sewer, the drainage piping of two (2) or more buildings located on the same lot and under one (1) ownership may be vented by means of piping sized in accordance with Table 710.1(1), provided the aggregate cross-sectional area of all vents is not less than that of the largest required common building sewer.
5-512 Section 917 of the International Plumbing Code and the indicated subsections are hereby amended to read as follows:
917.1 General. Vent systems utilizing air admittance valves shall comply with this section. Stack-type air admittance valves shall conform to ASSE 1050. Individual and branch-type air admittance valves shall conform to ASSE 1051.
917.2 Installation. The valves shall only be installed with prior approval from the Department Having Jurisdiction, in accordance with the requirements of this section and the manufacturer’s installation instructions. Air admittance valves shall be installed after the DWV testing required by Section 312.2 or 312.3 has been performed.
917.3 Where permitted. The valves shall only be permitted in the alterations of existing buildings with prior approval from the Department Having Jurisdiction. Individual, branch and circuit vents shall be permitted to terminate with a connection to an individual or branch-type air admittance valve. Stack vents and vent stacks shall be permitted to terminate to stack-type air admittance valves. Individual and branch-type air admittance valves shall vent only fixtures that are on the same floor level and connect to a horizontal branch drain. The horizontal branch drain having individual and branch-type air admittance valves shall conform to Section 917.3.1 or 917.3.2. Stack-type air admittance valves shall conform to Section 917.3.3.
917.3.1 Location of branch. The horizontal branch drain shall connect to the drainage stack or building drain a maximum of four branch intervals from the top of the stack.
917.3.2 Relief vent. Where the horizontal branch is located more than four branch intervals from the top of the stack, the horizontal branch shall be provided with a relief vent that shall connect to a vent stack or stack vent, or extend outdoors to the open air. The relief vent shall connect to the horizontal branch drain between the stack and the most downstream fixture drain connected to the horizontal branch drain. The relief vent shall be sized in accordance with Section 916.2 and installed in accordance with Section 905. The relief vent shall be permitted to serve as the vent for other fixtures.
917.3.3 Stack. Stack-type air admittance valves shall not serve as the vent terminal for vent stacks or stack vents that serve drainage stacks exceeding six branch intervals.
917.4 Location. Individual and branch-type air admittance valves shall be located a minimum of 4 inches (102 mm) above the horizontal branch drain or fixture drain being vented. Stack-type Air admittance valves shall be located not less than 6 inches (152 mm) above the flood level rim of the highest fixture being vented. The air admittance valve shall be located within the maximum developed length permitted for the vent. The air admittance valve shall be installed a minimum of 6 inches (152 mm) above insulation materials.
917.5 Access and ventilation. Access shall be provided to all air admittance valves. The valve shall be located within a ventilated space that allows air to enter the valve.
917.6 Size. The air admittance valve shall be rated in accordance with the standard for the size of the vent to which the valve is connected.
917.7 Vent required. Within each plumbing system, a minimum of one stack vent or vent stack shall extend outdoors to the open air.
917.8 Prohibited installations. Air admittance valves shall not be installed in nonneutralized special waste systems as described in Chapter 8 and in new construction. Valves shall not be located in spaces utilized as supply or return air plenums.
Exception: Island fixtures in new construction may be vented by air admittance valves that comply with section 917.
Section 3. SEVERABILITY.
If any section, clause, sentence, or phrase of this ordnance is found to be unconstitutional or is otherwise held invalid by any court of competent jurisdiction, it shall not affect the validity of any remaining parts of this ordinance.
Section 4. This ordinance shall be in full force and take effect on January 1, 2011, and after its publication as provided by law.
Passed by the Governing Body of the City of Lawrence, Kansas this ______ day of _____________, 2010.
________________________________
Mike Amyx, Mayor
ATTEST:
___________________________________
Jonathan M. Douglass, City Clerk
Approved as to form and legality:
___________________________________
Toni Ramirez Wheeler, Director of Legal Services