City of Lawrence

Mechanical Board of Appeals

June 27, 2007 minutes

 

MEMBERS PRESENT:

 

Jim Sparkes, Bryan Wyatt, Gary Mohr, Kevin Chaney

 

 

 

MEMBERS ABSENT:

 

Mark Jarboe

 

 

 

GUEST PRESENT:

 

None

 

 

 

STAFF PRESENT:

 

EX-OFFICIO:

 

Tim Pinnick, Plan Review Manager

 

Patrick O’Brien, Mechanical Inspector

 

 

 

 

Meeting called to order at 6:34 p.m.

 

Review and approve minutes from June 18, 2007 meeting

After review, Wyatt made a motion to approve the minutes as written.  Seconded by Mohr, pass 4-0.

 

Discuss plumbing board concerns

Chaney mentioned there was a Plumbing board meeting on July 18, 2007.  Chaney stated the reason he has mentioned the Plumbing board meeting is because the Plumbing board has decided unanimously to adopt the plumbing portions of the IRC, the IFGC and the IPC in it’s entirety without any amendments.  He stated that he spoke with staff members Barry Walthall, Tim Pinnick and Patrick O’Brien about his concerns and was advised to attend the next Plumbing board meeting to voice his concerns about the decision of the Plumbing board.  He mentioned his concerns with the IPC were the water supply pipe sizing, vent pipe sizing and no medical gas in the IPC.  He was planning on getting information from the IAPMO representative Bill Schweitzer of examples of problems that other jurisdictions have been experiencing with the IPC.  Chaney stated that Barry Walthall had explained the medical gas was a referenced standard in the IPC.

Mohr stated that if the Plumbing board was not planning to amend the IFGC regarding the gas pipe test pressure as the Mechanical board had discussed, he suggested proposing an amendment to change the test pressure requirements. 

Wyatt stated that since the Plumbing board has “jurisdiction” over the gas piping, maybe the Mechanical board should let the Plumbing board know the Mechanical board has a concern about it.

Chaney inquired from Mohr if he had experienced problems with water pipe sizing in the IPC.

Mohr responded they design over code minimums so they have not experienced any problems.

Wyatt suggested approaching the Plumbing board as a board and raise concerns about the gas pipe test pressure requirements.

Mohr made a motion proposing and amendment to 406.4.1, changing the minimum test pressure to 10 psi.  Seconded by Chaney.  Pass 4-0.

 

Wyatt asked if there was any reason given why there were not any amendments made to the codes.

Chaney stated that he had been told that since the international code had been forced on them, that they decided to just adopt the code as-is.  

Wyatt stated his concern would mainly be the gas pipe test pressures and that he would not have the expertise to question water pipe and vent pipe sizing.

Sparkes stated that he was surprised that there would be no amendments whatsoever.

Wyatt stated he is surprised that they would go from the number of amendments to no amendments.

 

Discuss the review of chapters 1-6 of the 2006 IMC

Staff mentioned to the board that chapter 1 will be deleted entirely and a local administration would be used and the administration of each trade would be combined.

Staff stated section 304.3 will be amended to reflect the existing amendment for elevation of ignition source.  Section 303.3 will need to add hot tub rooms to reflect the IRC.

Mohr asked about section 302.4 “Alterations to trusses” requiring approval from design professional before adding extra loads such as mechanical equipment and if the City is requiring compliance to this section.

Staff confirmed.

Chaney asked if that would be required even with a unit heater.

Staff stated there have been instances where contractors had to move equipment from the roof because engineers would not approve the application.

Sparkes asked if the requirement would include all types of equipment.

Staff responded most wood trusses are manufactured only for the ceiling load and the roof load and can not accommodate additional loading.

Chaney asked if they wanted to leave the requirement the way it is.

Pinnick responded to check to see if the trusses allow for storage and if so, a unit heater could be accommodated. 

 

Mohr stated his preference would be to leave section 304.3 the way it is written since it is covered in the IRC.  He moved to leave section 304.3 in the IMC and 305.3 in the IFGC as is.  Seconded by Chaney.  Pass 4-0. 

 

Chaney inquired about section 306.1.1 requiring 3” clearance around the sides and back of the furnace.

Wyatt replied the manufacturer allows zero clearance around the back and sides of the furnace but the code would be more stringent and would have to meet the requirement. 

Chaney stated he was mainly concerned about replacements and trying to obtain the clearance required would be difficult.

Staff replied that there is an exception that allows replacements as long as the manufacturer allows it.

Mohr stated on new construction, the requirement should stay.

Wyatt agreed that on new construction, the clearance should be maintained.

Chaney stated that if the requirement stays as it is, he knows of new construction installations have the furnace next to the wall.

Staff replied on closet installations, there is typically space to the side of the furnace to allow for the door jamb.

Chaney stated the back of the furnace is always against the wall with no space.

Pinnick stated when a plan is submitted, there will have to be the clearance according to the code section.

Staff stated there will be some training sessions to familiarize everyone with the new codes and that is one thing that can be mentioned.

The board decided not to take any action on the section.

 

Sparkes mentioned that section 307.2.3 in addition to requiring condensate overflow pans under cooling coils, condensing furnaces are required to have overflow pans also.

Wyatt stated that he knew of the pans under coils but not under the condensing furnaces.

Staff replied he had seen pans installed both ways, pans under only the coil and pans under the entire furnace.

Mohr stated he specs the whole unit to have a pan under it.

No action was taken by the board.

 

Mohr stated he would like to see a reference to ASHRAE 62 requirements for ventilation purposes and he would like to propose an amendment, but is not sure where it needs to be, so he will come back with a proposed amendment.

Chaney agreed to table section 403 for a proposed amendment.

 

Mohr stated he could not find the section where it prohibited positive pressure exhaust ducts in return air plenums and that requirement has always been present in the code.

Staff responded he would do some research on the issue.

Mohr was requesting more thought into allowing the small bathroom exhaust fans to vent through a plenum.  He stated he does not see the hazard in allowing a small bathroom exhaust fan to vent through the plenum to the outside. 

Staff stated he would look into the requirement.

 

Mohr recommended removing exception #1 from section 504.6 that allows the manufacturer recommendations to determine maximum dryer duct length for domestic clothes dryer ducts.

Chaney asked if they needed to amend both the IMC and the IRC.                                                                                 

Mohr made a motion to remove the exception from section 504.6 in the IMC and exception #1 in section 1502.6 in the IRC. Seconded by Wyatt.  Pass 4-0.

 

Mohr requested an explanation from ICC of section 506.3.2.5 requiring a pressure test on grease exhaust ducts prior to operation or concealment. His questions were is the City prepared to enforce that provision and is the provision really necessary.  He agrees a light test is needed, but a pressure test seems to be stringent.

Wyatt suggested submitting the question to ICC.

Mohr asked about the change in requirement of air velocity in section 506.3.4.

The board tabled both sections and requested staff check with ICC on both issues.

 

Mohr had a question about pizza ovens on weather they required to have a type I hood or a type II hood.

Wyatt responded there has been discussion in the past concerning the pizza oven hoods and explained most of the meats are pre-cooked and don’t produce large amounts of grease.  The main focus of the oven is to melt cheese and cook the bread.

Mohr stated if a pizza oven is required to have a Type I hood, he would like to see pizza ovens listed under appliances required to have Type I hoods.

Pinnick stated he had called an oven manufacturer about the hood requirement and was told people have purchased a pizza style oven to bake bricks.

Staff stated open type conveyor ovens would allow the vapors to escape and would require a Type I hood; the enclosed slab type oven would require a Type II.  The concern was the fire department was not requiring fire suppression for the Type I hood system.  The fire department will now require a fire suppression system in any Type I hood.

Wyatt stated if there is a grease issue and a Type I hood is required, there should be fire suppression required also.  If it is determined pizza ovens do not produce the grease, a Type I should not be required.

Mohr stated all pizza ovens can not be placed into a warming category.  The reason he brought it up is because all ovens in general are under the Type I requirement.  If pizza ovens require Type I he said did not have a problem with that.

Wyatt stated he will not argue pizza ovens are required to have Type I, but if it is a Type I hood, it should have fire suppression and grease trap.

The board agreed the code is sufficient that a Type I hood requires fire suppression.

 

Mohr asked what the stand is on domestic ranges in commercial buildings such as office break rooms or church kitchens. 

Staff replied a domestic range that is not in a food processing establishment would not require a commercial exhaust system.

Mohr stated there is not an exception that would allow that particular application. 

Pinnick stated there will be some situations where it will be acceptable to have a domestic range in a commercial building without a Type I or II hood.  The main question will be to determine the use when plans are submitted.

The board agreed to leave the determination up to the jurisdiction.

 

Mohr stated he had a problem with section 601.2 and suggested deleting exception #3.  He stated using corridors for return air in larger occupancies had been removed from the code years ago.

Pinnick stated if it is a rated corridor, the corridor could not be used as a plenum.

Mohr motioned to delete exception #3 in section 601.2.  Seconded by Wyatt.  Pass 4-0.

 

Mohr suggested in section 602.2 to add humidifiers to the prohibited items in systems with gypsum products.  His concern is with placing moisture into a system with gypsum and creating a mold situation.  A similar addition would be required in 603.5.1.

Mohr made a motion to add “humidifiers” to the above mentioned sections.  Seconded by Chaney.  Pass 4-0.

 

Mohr made a suggestion in Table 603.4 to change the minimum 30 gage for rectangular ducts to a minimum 28 gage.

 

Staff informed the board flexible air connectors are allowed in the IMC and have not been allowed in the UMC.  Air connectors don’t pass the flame spread index rating in the UMC. 

Chaney made a motion to remove any reference of air connector from the code.  Seconded by Wyatt.  Pass 4-0.

 

Chaney stated there was discussion in the past about requiring better access for fire and smoke dampers.

Staff replied there had been discussion on drafting an amendment, but one had not been added to the code.

Chaney suggested amending section 607.4 requiring 18”x18” minimum access opening in hard ceiling and minimum 144 square inches access in ductwork. 

Mohr stated on ducts smaller than 12” to require a portion of the duct to be removable.  

Staff stated they would draft language and bring it to the next meeting.

The board took no action.

 

Miscellaneous

The board discussed reviewing 7-14 for next meeting and next meeting on July 16th.

 

Adjourn

Motion to adjourn made by Mohr, seconded by Wyatt, passed 4-0.  Meeting adjourned at 8:27 p.m.